Purpose:The purpose of this test is to show the effect upon access floor panels and supporting understructure system(s) when subject to impact from heavy loads being accidentally dropped onto the floor panel. Preparation:Test(s) shall be performed on three (3) randomly selected bare panels placed on an understructure support system that is configured identical to an installed system. Any stringers, coatings, gaskets, pads, clips, fasteners, locking devices or other materials normally used shall be configured identical to that provided in an installed system. The test mock-up configuration shall be at a finished floor height suitable for the system being tested. A safety-restraining device may be utilized for load constraint to prevent possible injuries, providing it does not restrict the purpose of the test. The load to be dropped shall be either a single hard object or objects placed inside a rigid container that will not flex or distort during the impact of the test. The load shall be dropped vertically from a given height onto the center of a steel "impact" plate of not less than one-half inch (1/2") [12.7 mm] thick x eight inches (8") [20.3 mm] square that is placed centrally on top of a one inch (1") [25.4 mm] square steel indentor not less than one-half inch (1/2") [12.7 mm] thick.
|
|
Test Procedure:
|
Contact: Patrick Chen
Phone: +86-18861159966
Tel: +86-18861159966
Email: info@maxgrid.com